- #Firelite voice evac manuals
- #Firelite voice evac install
- #Firelite voice evac manual
- #Firelite voice evac series
Fire-Lite manufactures fire alarm control panels (FACPs), EV. Complete the installation by connecting the AC power wires to the Hot, Neutral and Earth terminals of TB1 on the Power Supply/Battery Charger Module. Fire-Lite Alarms is an American company owned by Honeywell and based in North ford, Connecticut. Note that the Transformer cable connector is keyed to prevent connection. Plug the XRM-24(E) Transformer cable assembly into connector P1 which is located in the lower left corner of the Power Supply/Battery Charger Module. This connection is in order to provide proper lightning and transient protection for the panel.

Connect a wire from a solid earth ground to one of the Transformer mounting studs and tighten the nut. Do not tighten one nut until the next step. Secure Transformer to the studs with the two supplied nuts. Transformer should be oriented so the cable assembly is the left as illustrated below. Position XRM-24(E)Transformer Assembly over mounting studs. Transformer Installation Locate two threaded mounting studs in the bottom left corner of the backbox (refer to backbox illustration below).
#Firelite voice evac install
2, 3 Standoff 1, 2, 3 factory jumper installing the Module 2, 3 Standoff 1, 2, 3 Standoff Power Supply/ Charger Module Evacuation Control Panel Circuit Board Remove two mounting screws from main board upper and lower left corners Main Circuit Board Install four metal standoffs by screwing place (note two different lengths) Install FC-PSM(E) Module and with four screws Circuit Main Circuit Board Backbox Mounting Rails Backbox Mounting Rails Backbox Mounting Rails Make certain all power (AC and DC) is removed before any connections are made. Continue with the FC-PSM(E) transformer installation as described on the following page. It is important that module be secured with the metal screws in order to help protect against lightning electrical transients. Secure the FC-PSM(E) to the standoffs using the two screws removed in Step 1 and two supplied screws. Make certain the pins are properly aligned to prevent bending or any pins. Carefully align connector J1 on the FC-PSM(E) Power Supply/Battery Charger Module with connector P7 on the main board and press the FC-PSM(E) securely into place. P7 is located on the bottom left corner the main circuit board (refer to illustration below).
#Firelite voice evac series
Fire Lite SD-365 Series Fire Lite ECC 50/100 Emergency Command Center Voice Evac. The mounting studs are located to the far left on each rail (refer to illustrations on following Remove the factory installed jumper from connector P7 of the main circuit board. Fire-Lite MS-9600UDLS 318 point (expandable to 636 points) addressable panel. Install the two supplied long metal standoffs by screwing them onto the threaded mounting studs in the top and bottom rails in the back box. Install two short metal standoffs, which are supplied with the FC-PSM(E) Power Supply/Battery Charger Module, by screw- them into the top left and bottom left corners of the main circuit board, where the screws were removed in Step 1. Power Supply/Battery Charger Module Installation Remove two mounting screws from the top left and bottom left corners of the main circuit board (largest circuit board closest to cabinet back). Evacuation Control Panel Power Supply/Battery Module Installation Drawing 50612 Rev B 8/8/97 ECN 97-303 Make certain all power (AC and DC) is removed before any connections are made. In addition to supplying operating the modules are capable of charging 7 AH to 17 AH batteries. The FC-PSME requires VAC, 50 Hz, 0.5 amps. The 9200ud panel has a card that you rotate depending on if it's class a or class b but I can't find anything on the voice evac panel so I'm guessing you just either wire it as a or b and it'll knowThe FC-PSM(E) Power Supply/Battery Charger Module can be used to stand-alone power to the Voice Evacuation Control Panel. However both indicate a trouble condition.
#Firelite voice evac manual
From reading the manual I either need to have the EOL 4.7k across the terminals of the speaker or a loop back to 5 and 6 depending on the class. I've got it on the bench with a speaker connected to the amp module to the terminal block and connection 3 and 4 per the diagram.
#Firelite voice evac manuals
I've got all the associated manuals and theoretically for now have programmed the voice evac system (the acc25/50) to operate stand alone via the dip switches. I received a 9200UD, an AAC25/50, a distributed audio pannel and some accessories like strobes / horns / address modules, pulls, etc.

Well that is to say I've always been interested but finally am working on learning more. So I'm beginning to learn about fire alarm systems. UPC 783008105266 is associated with product Fire-Lite Alarms / Honeywell - ACC-25/50 - Audio Cmnd Cntr Voice Evac Pnl, find 783008105266 barcode image.